Flow control, or metering, of the refrigerant is accomplished by use of a temperature sensing bulb, filled with a similar gas as in the system, that causes the valve to open against the spring pressure in the valve body as the temperature on the bulb increases. As the suction line temperature decreases, so does the pressure in the bulb and therefore on the spring causing the valve to close.
The pressure spring can be adjusted to increase or decrease pressure based on temperature needs. The pressure created by the spring acts on the opening of the valve. When the pressure of the sensor bulb acting on the diaphragm is greater than the combined pressure of the evaporator and spring, the valve opens to increase the flow rate of the working fluid. An increase of flow rate lowers the temperature of the evaporator and allows for more heat absorption.